Quick answer
Multiply the power your essential loads draw (in kW) by the hours you want backup, then divide by the usable share of the battery (about 0.8 to 0.9 for LiFePO₄) to get the battery size in kWh.

On this page: The formula behind every battery size · How to size a battery: step by step · Worked example one: a fan, light, TV, fridge and router load · Worked example two: adding an air conditioner · How to size a battery bank: 12V, 24V or 48V, series or parallel · Lithium or lead-acid: how the chemistry changes the size · Linking the battery to your solar panels · Common mistakes to avoid · Frequently asked questions · How to size a battery with confidence
Here is how to size a battery in one sentence: multiply the watts you want to run by the hours you want them to run, divide by the share of the battery you can safely use, then add a margin for inverter losses. The result is the battery capacity you need in watt-hours, which you can then convert into amp-hours for the voltage of your system.
That sounds neat on paper, but most of the confusion we meet in the shop comes from the details: what is a watt-hour, why does a lead-acid battery only give you half of its label, and why does a 2kVA IPS not run two kilowatts of air conditioning? In this guide on how to size a battery, we take each piece slowly, work through two complete examples, and finish by tying the battery to your solar panels so the whole system hangs together.
The formula behind every battery size
Before any example, let us define the words so nothing feels like jargon.
- Watt (W) is how fast an appliance uses energy at a given moment. A fan might use 60 W.
- Watt-hour (Wh) is energy: one watt used for one hour. A kilowatt-hour (kWh) is 1,000 Wh, the same unit your electricity meter counts.
- Amp-hour (Ah) is how batteries are labelled. Multiply Ah by the battery voltage and you get Wh. So a 12V 100Ah battery holds 12 x 100 = 1,200 Wh.
- Depth of discharge (DoD) is how much of the battery you drain in one go. If you use 50 Wh from a 100 Wh battery, the DoD is 50 percent. You can read a short background on depth of discharge on Wikipedia.
Put it together and the working formula is:
Battery size (Wh) = load (W) x backup hours / inverter efficiency / usable DoD
Inverter efficiency is the share of battery energy that actually reaches your appliances; the rest becomes heat. Use roughly 0.85 to 0.90 as a planning number. Usable DoD is about 0.5 for lead-acid and 0.8 to 0.9 for LiFePO4 lithium. Those are general rules of thumb; your battery datasheet has the exact recommendation.
How to size a battery: step by step
Follow these six steps in order to learn how to size a battery without guesswork. Each one is simple on its own, and together they stop you from buying a battery that is too small or a bank you do not need.
- Decide what must run. Make a list of the appliances you want during an outage. Be strict. Lights, fans, a TV, a fridge and a router are cheap to back up. A water heater or iron is not.
- Find each appliance’s watts. Check the label on the back or the manual. If you only see amps, multiply by the mains voltage (about 220 V) to get watts.
- Add them up. That is your load in watts. Include a small margin for starting surges.
- Choose backup hours. Think of your usual load-shedding length, then add some buffer for bad days.
- Apply efficiency and DoD. Divide by 0.85 to 0.90, then by the usable DoD of the chemistry you choose.
- Convert to Ah at your system voltage. Divide the final Wh by 12, 24 or 48, depending on the inverter’s battery voltage.
If you want to see this applied to a ready-made product line, our home IPS and lithium battery pages list the capacities we stock, so you can match your result to a real size.
Finding real watts when the label is vague
Labels often show the maximum rating, not what the appliance draws day to day. A ceiling fan on low speed uses far less than on high, and an LED TV uses less than the figure printed for its brightest setting. If you want accuracy, a plug-in energy meter from any electronics shop shows the actual watts. Measure the fridge over a few hours, because its draw swings as the compressor cycles.
When in doubt, round up. A slightly larger battery costs a little more, while a battery that is too small means lights going out at 10 p.m. with the fan still needed until sleep.
Worked example one: a fan, light, TV, fridge and router load
This is the everyday case when people ask how to size a battery: a flat where you want the basics running through load-shedding.
How to size a battery for a basic household load
| Appliance | Quantity | Watts each | Total watts |
|---|---|---|---|
| Ceiling fan | 3 | 70 | 210 |
| LED light | 6 | 9 | 54 |
| TV | 1 | 80 | 80 |
| Refrigerator (running average) | 1 | 120 | 120 |
| Wi-Fi router | 1 | 12 | 12 |
| Total | 476 |
We round 476 W up to 480 W. Now we want 4 hours of backup.
- Energy needed = 480 W x 4 h = 1,920 Wh.
- Allow for inverter efficiency of 90 percent: 1,920 / 0.9 = 2,133 Wh from the battery.
With LiFePO4 at 90 percent usable: 2,133 / 0.9 = 2,370 Wh. A single 51.2V 50Ah battery stores 51.2 x 50 = 2,560 Wh (2.56 kWh), so one unit covers it with a little left over.
With lead-acid at 50 percent usable: 2,133 / 0.5 = 4,267 Wh. On a 24V system that is 4,267 / 24 = about 178 Ah, so you round up to two 12V 200Ah batteries wired in series, giving 24V 200Ah, which is 4,800 Wh.
One honest caveat: a fridge does not run continuously. The compressor cycles on and off, so 120 W is an average, and it draws more at the moment it starts. That is why we kept a margin and why the inverter should be comfortably bigger than the 480 W load.
Worked example two: adding an air conditioner
When you are learning how to size a battery, an AC changes everything, because it is the biggest load in most Bangladeshi homes. Let us add one 1.5-ton split AC to the same flat for 3 hours at night. As a planning figure, assume it draws about 1,100 W on average once the compressor is cycling; check your unit’s nameplate because models differ widely, and inverter-type ACs are gentler than fixed-speed ones.
Step by step
- Total load = 480 W + 1,100 W = 1,580 W.
- Energy = 1,580 W x 3 h = 4,740 Wh.
- With 90 percent efficiency: 4,740 / 0.9 = 5,267 Wh.
LiFePO4 (90 percent usable): 5,267 / 0.9 = 5,852 Wh. A 51.2V 100Ah battery (5.12 kWh) is not quite enough, so add a 2.56 kWh unit: 5.12 + 2.56 = 7.68 kWh. That covers the AC night with room to spare.
Lead-acid (50 percent usable): 5,267 / 0.5 = 10,534 Wh. At 48V that is 10,534 / 48 = about 220 Ah, so four 12V batteries of 220Ah or more in series. It is a big, heavy bank that needs ventilation and floor space.
Look at the inverter too. The AC compressor draws several times its running power for a moment at start-up, and the total load is already 1,580 W. A 3 kW or larger pure sine wave inverter is the sensible class. This is why many families back up the fans and lights on batteries and run the AC from solar during the day or from the grid, rather than building a huge battery just for the AC.
If the numbers for the AC are surprising, you are not alone. When the load is large or outages are long, a diesel generator is sometimes the practical partner; we discuss that in our note on diesel generator sizing in kVA and kW.
How to size a battery bank: 12V, 24V or 48V, series or parallel
The voltage of your battery bank, the next piece of how to size a battery, is set by the inverter you buy, not by taste. Small IPS units commonly use 12V or 24V, mid-sized ones 24V or 48V, and hybrid solar inverters usually 48V.
Why does this matter? Current. Current (amps) equals power divided by voltage, and high current means thick cables, hot connections and losses. Take the 1,580 W AC example:
- At 12V: 1,580 / 12 = about 132 A. Very heavy cables, not practical.
- At 24V: 1,580 / 24 = about 66 A.
- At 48V: 1,580 / 48 = about 33 A. Much easier on wiring and safer.
So as the load grows, move to a higher voltage rather than forcing more current through thin copper.
Series and parallel in plain words
Series connection adds voltage and keeps the amp-hours the same. Parallel connection adds amp-hours and keeps the voltage the same. Suppose you have four 12V 100Ah batteries:
- All four in series: 48V 100Ah = 4,800 Wh.
- All four in parallel: 12V 400Ah = 4,800 Wh.
- Two in series, two such strings in parallel: 24V 200Ah = 4,800 Wh.
The energy is identical; only the electrical shape changes. Always match the final voltage to the inverter. Mix only batteries of the same type, same capacity and, ideally, same age. Lithium batteries such as a 51.2V 100Ah unit already come at 48V class, so you add more units in parallel to grow capacity, following the maker’s rules.
Lithium or lead-acid: how the chemistry changes the size
How to size a battery also depends on chemistry, because the same load needs different amounts of rated battery depending on what you choose. The table below uses the 2,133 Wh requirement from example one.
| Item | Lead-acid tubular | LiFePO4 lithium |
|---|---|---|
| Usable share of rated capacity | About 50% | About 80% to 90% |
| Rated size for 2,133 Wh | 2,133 / 0.5 = 4,267 Wh | 2,133 / 0.9 = 2,370 Wh |
| Typical real unit | Two 12V 200Ah in series (4.8 kWh) | One 51.2V 50Ah (2.56 kWh) |
| Space and weight | Larger and heavier | Smaller and lighter |
| Upkeep | Water top-ups, ventilation | Little routine care |
| Upfront cost per rated kWh | Lower | Higher |
Neither is wrong. If you use backup only a few hours a week and money is tight, lead-acid on an IPS is a fair answer. If you cycle the battery every day with solar, lithium’s deeper usable range and lower upkeep usually make more sense. We compare them at length in our guide to LiFePO4 vs lead-acid batteries, and if you are still deciding between a basic IPS and a solar hybrid inverter, read IPS vs solar hybrid inverter for load-shedding.
Linking the battery to your solar panels
A battery only holds energy; something must refill it. With a plain IPS that is the grid. With a hybrid solar setup it is the panels, so the battery and the array have to be planned together.
The method for how to size a battery for solar is short. Take the energy you draw from the battery each day, allow for charging losses, and divide by what a kilowatt of panels yields. In Bangladesh, a 1 kWp array (kilowatt-peak, its rated output) typically gives about 3.5 to 4.5 kWh a day after losses.
Example one, continued
- Battery energy drawn per outage: 2,133 Wh.
- Allow about 90 percent charging efficiency: 2,133 / 0.9 = 2,370 Wh, or 2.37 kWh.
- Panels: 2.37 / 4.0 = about 0.6 kWp. At 4.5 kWh per kWp it is 0.53 kWp, at 3.5 it is 0.68 kWp.
A single 550 W or larger panel can refill that battery on a sunny day, though it would then have nothing left for the daytime load.
Example two, continued
- Battery energy: 5,267 / 0.9 = 5,852 Wh, about 5.85 kWh.
- Panels: 5.85 / 4.0 = about 1.46 kWp (range 1.3 to 1.7 kWp).
- With 550 W panels: 1,460 / 550 = 2.7, so 3 panels, or 1.65 kWp.
Remember the array also feeds your daytime load first. If you want to power the house and refill the battery, add that daytime use to the sum, and the array grows. Our guide on how many solar panels a 5kW system needs shows the panel arithmetic in more detail, and the hybrid inverter range is where this planning ends up in hardware. If you would rather start from tested combinations, see our solar packages.
Common mistakes to avoid
Most mistakes in how to size a battery come from skipping one of the steps above.
- Using the battery label as the usable capacity. A 200Ah lead-acid battery is not 200Ah for daily use. Plan on about half.
- Forgetting inverter losses. Skipping the efficiency step makes backup hours fall short.
- Adding VA instead of watts. Appliances are listed in watts; a 2kVA inverter does not necessarily give 2,000 W of real power.
- Ignoring starting surges. Fridges, pumps and ACs spike at start-up. The inverter must handle the surge, not just the average.
- Choosing 12V for a big load. Heavy current heats cables and wastes energy. Step up the voltage.
- Mixing battery ages or types. One weak battery drags the whole bank down.
- Sizing for the best day only. Monsoon cloud and long outages happen. Add a buffer of an hour or so.
- Forgetting temperature. Batteries in a hot cupboard age faster, whatever the chemistry.
- Buying a bank first and the inverter later. The inverter sets the voltage and the maximum power, so decide it together with the battery.
Frequently asked questions
How many batteries do I need for a 1000 watt load?
It depends on the hours. For 3 hours at 1,000 W you need 3,000 Wh, so about 3,333 Wh after 90 percent efficiency. At 50 percent usable lead-acid that means about 6.7 kWh of rated capacity (for example four 12V 150Ah batteries, 7.2 kWh in total), or about 3.7 kWh of rated lithium at 90 percent usable.
How do I calculate battery backup time?
Multiply battery Ah by voltage to get Wh, multiply by the usable DoD and the efficiency, then divide by the load in watts. For a 12V 200Ah lead-acid battery: 2,400 x 0.5 x 0.9 = 1,080 Wh, so a 300 W load runs about 3.6 hours.
How long will a 100Ah battery last?
A 12V 100Ah battery stores 1,200 Wh. At 50 percent usable and 90 percent efficiency, that gives 540 Wh, so a 100 W load runs about 5 hours. At 300 W, it runs about 1.8 hours.
What size battery do I need for a 1.5 ton AC?
Plan on roughly 1,000 to 1,500 W running and a larger start-up surge. For 3 hours that means several kWh of usable battery, as in our second example, around 7 to 8 kWh of lithium. Check your AC’s nameplate and consider running it from solar by day.
Can I connect batteries of different sizes?
It is best not to. Mismatched capacity or age leads to uneven charging, and the weakest battery limits the bank. Use identical units bought together.
Is 48V better than 12V for home backup?
For anything beyond small loads, yes. The same power at 48V draws a quarter of the current, so wiring runs cooler and losses are smaller. Most hybrid inverters use 48V for this reason.
How to size a battery and solar panels together?
Divide the battery energy you use daily, plus a little for charging losses, by about 3.5 to 4.5 kWh per kWp. Then divide by the panel wattage. Add your daytime load if the panels must run the house at the same time.
Does a bigger battery always mean longer backup?
Only if the inverter can also carry the load. A large battery behind a small inverter will still trip when you overload it. Size the battery and the inverter as a pair, and for common questions, our FAQ page may help.
How to size a battery with confidence
To recap how to size a battery: list the essential watts, multiply by the hours, divide by inverter efficiency and usable depth of discharge, pick the system voltage that matches your inverter, and check that your solar array can refill what you take out. Do the sum for lithium and for lead-acid, and let the numbers, not the sales pitch, guide you.
If you would like a second pair of eyes, call +880 1712-567878 or message GPTECH on WhatsApp for a free site survey and quotation. We supply genuine, warranty-backed batteries, inverters and panels, and deliver across Bangladesh. You can also read how our team handles installation and site surveys before you decide.
Frequently asked questions
What is the formula?
Battery size in kWh = load in kW x backup hours / usable depth of discharge, for example 1 kW x 5 hours / 0.9 is about 5.6 kWh.
How do I find my load?
Add up the watts of the appliances you want to run together, such as fans, lights, TV, router and fridge, then divide by 1000 to get kW.
Should I add a safety margin?
Yes, allow some extra for inverter losses and battery ageing; our engineers can size it for your appliances.
Does the inverter size matter?
Yes. The inverter must be able to supply the combined load at once, including start-up surges from motors such as ACs and pumps.
Related products
-
SolaX
SolaX 3kW Single Phase Low Voltage Hybrid Solar Inverter
৳100,100 In stock -
SolaX
SolaX 5kW Single Phase Low Voltage Hybrid Solar Inverter (SREDA approved)
৳121,000 In stock -
SolaX
SolaX 10kW Three Phase Low Voltage Hybrid Solar Inverter
৳242,000 In stock -
SolaX
SolaX 15kW Three Phase Low Voltage Hybrid Solar Inverter
৳288,200 In stock